ETABS Load Input Mistakes: How to Audit Loads by Storey

Quick answer: The most damaging ETABS mistakes on tall buildings are load input errors, not modelling theory: a value typed ten times too large, a floor with no loads at all, or a heavy landscape load spread over the whole slab. Find them by auditing loads storey by storey: get each load pattern's storey totals from the Story Forces table, divide by floor area to get kPa, and compare each storey with its neighbours and with a hand build-up of the expected floor weight. On a real 50+ storey tower, this audit found about 10,000 t too much at the roof and about 15 MN missing on the transfer slab in under an hour.
ETABS load audit by storey: SDL per floor with a roof spike, a missing-load floor above the transfer slab, a landscape step and fill on the ground slab, beside the expected typical floor weight build-up of about 15 kPa


This is the second post in our From a Real Tower Project series. In the first, the ETABS model review checklist, the six biggest findings on a residential tower of more than 50 storeys came out of the loads. Here is exactly how those errors were found, why ETABS cannot catch them for you, and a repeatable load audit you can run on any model. Project details have been removed and the figures rounded.

Why load errors are so dangerous

A wrong load does not trigger a warning. The model still runs, converges and produces tidy results. But on a tall building, one wrong number moves almost everything:

  • Mass: loads feed the seismic mass, so the periods, mode shapes and earthquake forces change.
  • Gravity: wall and column axial forces, transfer slab design and pile loads change.
  • P-Δ: extra weight high up increases second-order effects and drift.

An error near the top hurts most, because weight at the roof has the longest lever arm in both seismic and P-Δ effects.

The five load mistakes we found

MistakeWhereSize of the errorHow it showed up
SDL typed as 40 kPa instead of about 4 kPaWhole roofAbout +10,000 t at the topRoof mass more than 3 times a typical floor
No SDL, partitions or live loadFirst floor above the transfer slabAbout 15 MN missing on the transfer slabOne floor much lighter than every floor above it
30 kPa landscape load over the whole podium roofIncluding the area covered by the towerLoad where no soil can existPodium roof SDL far above the floors below
Fill load on a ground-level slabLowest suspended levelThousands of tonnes of extra seismic massHeavy mass 2 m above the base
Live loads not matched to useCorridors, lobbies, drop-off areasToo low (1.5 kPa where 3–5 kPa applies)Uniform live load on every floor regardless of use

None of these is exotic. A slipped decimal point, a floor skipped when copying loads up the building, and one load polygon drawn over the whole slab instead of the planters: every model in every office is exposed to them.

Step 1: Build the expected floor weight by hand

Before opening a single table, work out what a typical floor should weigh. This is your yardstick. For the wall-bearing residential floors of the tower, the build-up looked like this (seismic mass, per m² of floor):

ComponentBasiskPa
Slab150 mm × 24 kN/m³3.6
Wallsabout 0.33 m of 200 mm wall per m² of floor, 2.9 m high, 24 kN/m³4.6
Cores and thicker wallsLift and stair coresabout 1.5
BeamsSmall downstand beams0.6
SDL (finishes, services)As specified1.2
PartitionsLine loads, converted to an equivalent uniform loadabout 3.2
Live load in the mass0.3 × 1.5 kPa0.45
Expected totalabout 15 kPa

ETABS gave about 15–16 kPa for a typical tower floor, so those floors were fine. The hand build-up takes ten minutes and tells you instantly whether a floor is plausible. Your numbers will differ with the structure: a flat-slab office floor may come out at 8–11 kPa, a wall-dense residential floor at 12–18 kPa.

Step 2: Get storey totals for each load pattern

The fastest way to get the load on each storey, without adding up hundreds of shell loads, is to let ETABS do it:

  1. Make sure every load pattern (Dead, SDL, Live, partitions) has its own load case, which ETABS creates by default.
  2. Run the analysis (a linear static run is enough; it takes minutes even on a big model).
  3. Open Display > Show Tables > Analysis Results > Structure Results > Story Forces and choose the gravity load cases.
  4. Export to Excel. The P column at the bottom of each storey is the cumulative load from that storey upwards.
  5. Subtract consecutive storeys to get the load on each storey, then divide by the floor area.
Load on storey i = Pbottom, i − Pbottom, i+1
Equivalent pressure (kPa) = load on storey (kN) ÷ floor area (m²)

Do this for SDL, live and partitions separately. A single column of kPa values per load pattern, one row per storey, makes errors jump out. Also check Base Reactions: the total for each gravity pattern must equal the sum of the storey loads.

Step 3: Plot it and look for spikes and gaps

Plot each load pattern's kPa against storey. On a healthy model the typical floors form a flat, boring line. The errors looked like this:

  • Spike: the roof SDL bar was ten times longer than every other storey. A real roof SDL is about 2–4 kPa for screed, waterproofing and services. Tanks and plant should be applied as local loads where they sit.
  • Gap: the first floor above the transfer slab showed zero SDL, zero partitions and zero live load. It was not a refuge or plant floor; the loads had simply never been assigned.
  • Step: the podium roof SDL was 30 kPa across its full area. Planting soil of about 1.5 m only exists in the planters, never under the tower footprint.

Then check the Mass Summary by Story table the same way. Mass errors and load errors usually appear together, because SDL and partitions are part of the mass source.

Step 4: Check every unusual value has an owner

Sort the Shell Loads – Uniform and Frame Loads – Distributed tables by value, largest first. For every value outside the normal range, write down what it represents and who confirmed it. In our review this turned up:

  • line loads of 25–30 kN/m on a few beams per floor that nobody could immediately explain (probably a lift, stair or riser, but unconfirmed);
  • partition line loads of about 8 kN/m (3.0 kPa × 2.65 m of brick) on small beams, which were checked to make sure none sat on top of a wall;
  • a 10 kPa SDL on two lower podium levels, which needed a reason.

“Nobody knows what this load is” is a finding in its own right. Ask before you delete anything: some odd loads are real.

Step 5: Fix, re-run and re-plot

After corrections, run the same audit again. The plot should show flat typical floors, a sensible roof, and only explained steps at plant, transfer and podium levels. Then move on to the rest of the model review: supports, combinations, seismic and wind, as covered in the 30-check checklist.

Load audit checklist

CheckPass if
Hand build-up of a typical floorETABS mass within about 10% of your estimate
SDL per storeyEvery storey has a value, and steps are explained
Live load per storeyMatches the use of each area (3.0 kPa for corridors and lobbies in flats, 2.5 kPa car parks, 5 kPa or more for heavy-vehicle areas)
PartitionsOn every occupied floor, not on top of walls
Heavy loads (soil, fill, tanks, plant)Only where they really are
Ground-bearing slabsLoads on grade are not in the structural model or mass
Base reactionsEach gravity pattern total equals the storey sum and your estimate
Largest values in each load tableEvery one explained and confirmed

New to ETABS? Start with the ETABS tutorial for a multi-storey RC building. For material weights used in the build-up, see concrete grades and the density of steel.

FAQ

How do I check the total load in ETABS?

Run the analysis and open the Base Reactions table. The vertical reaction for each gravity load case is the total of that load. Compare it with floor area × expected kPa, summed over all floors.

How do I see the load on each floor in ETABS?

Use the Story Forces table for each gravity load case. The axial force P at the bottom of a storey is the cumulative load from that storey up; subtract consecutive storeys to get each floor's load.

What is a typical superimposed dead load on a roof?

About 2–4 kPa for screed, insulation, waterproofing and light services. Water tanks, plant and roof gardens are much heavier and should be applied locally where they sit, not over the whole roof.

Should a ground-bearing slab load be in the ETABS model?

No. Loads carried directly by the ground do not pass through the structure and should not be in the seismic mass. Only model the slab if it is suspended.

References

  • CSI, ETABS User's Guide (Story Forces, Base Reactions and Mass Summary tables).
  • EN 1991-1-1:2002, Eurocode 1, Tables 6.1–6.2 and 6.7–6.8 (imposed loads by category) and Annex A (densities).
  • BS 6399-1:1996, Loading for buildings, Table 1 (imposed floor loads).

Written by Engr. Abdul Latif, Senior Structural Engineer, from a real tower model review. Project details have been removed and figures rounded. Published November 2026.